NoteAction
If the robot is to be calibrated with fine
calibration:
Remove all external cable packages
(DressPack) and tools from the robot.
Removal
The procedure below details how to remove the cable harness, axes 1-2.
NoteAction
Decide which calibration routine
to use, and take actions accord-
ingly prior to beginning the re-
pair procedure.
1
In order to facilitate refitting of
the cable harness, run the robot
to the specified positions:
Axis 1:
Axis 2:
Axis 3:
Axis 4:
Axis 5: +90°
Axis 6: no significance
2
DANGER
Turn off all:
electric power supply to
the robot
hydraulic pressure sup-
ply to the robot
air pressure supply to
the robot
Before entering the robot work-
ing area.
3
Shown in the figure Location of cable harness, axes
1-2 on page 185.
Remove the top cover, connec-
tion box from the robot by re-
moving its attachment screws.
4
Continues on next page
Product manual - IRB 6620 187
3HAC027151-001 Revision: T
© Copyright 2006-2018 ABB. All rights reserved.
4 Repair
4.3.1 Replacement of cable harness, lower end (axes 1-2)
Continued