MEASUR EMEN TS PROD UCT FU NCTI ONS
1TNC9 2825 0M0201 18
3.1 Measurements
Description
Range
Accuracy (accord. to
IEC 61557-12)
Voltage U1
30 to 400 VAC ph/n
0.2
Voltage U2
30 to 400 VAC ph/n
0.2
Voltage U3
30 to 400 VAC ph/n
0.2
Voltage U12
50 to 690 VAC ph/ph
0.2
Voltage U23
50 to 690 VAC ph/ph
0.2
Voltage U31
50 to 690 VAC ph/ph
0.2
Current I1
5 % to 120 % In
0.2
Current I2
5 % to 120 % In
0.2
Current I3
5 % to 120 % In
0.2
Current Neutral I
N
5 % to 120 % In
1
Current Unbalance I
unb
%
na
Voltage Unbalance u
unb
%
na
Power factor PF
0.5 ind to 0.8 cap
0.5
Frequency F
45 to 65 Hz
0.1
Active power L1- P1
2 % to 120 % In
0.5
Active power L2-P2
2 % to 120 % In
0.5
Active power L3-P3
2 % to 120 % In
0.5
Total active power P
2 % to 120 % In
0.5
Reactive power L1-Q1
2 % to 120 % In
0.5
Reactive power L2-Q2
2 % to 120 % In
0.5
Reactive power L3-Q3
2 % to 120 % In
0.5
Total reactive power Q
2 % to 120 % In
0.5
Apparent power L1-S1
2 % to 120 % In
1
Apparent power L2-S2
2 % to 120 % In
1
Apparent power L3-S3
2 % to 120 % In
1
Total apparent power S
2 % to 120 % In
1
* All listed values above are displayed through HMI MP53/MP56 and accessible via communication.