A .1 T ECHNI CAL SP ECIFI CATI ONS CONFIG URAT ION
1TNC9 2825 0M0201 51
Auxiliary power supply
Rated operational voltage (Ue)
110-240 VAC
Voltage operation range
85 %-110 % Ue
Rated frequency
50 / 60 Hz
Power consumption
16 VA max. @ 240 VAC
8 VA max. @ 110 VAC
Power output
Current
100 mA @ 240 VAC supply input
50 mA @ 110 VAC supply input
Voltage
24 VDC
Terminal wire area
0.2 .. 2.5 mm
2
Recommended tightening torque
0.5 .. 0.6 Nm
Relay output
Rated operation voltage (Ue)
24 or 110 VDC, 110 or 240 VAC
Rated operation current (Ie)
2A /24 VDC(DC-13)
0.1A/110 VDC(DC-13)
4A/120 VAC(AC-15)
2A/240 VAC(AC-15)
Digital inputs
Voltage
24 VDC
On
Voltage: 15 V < V < 30 V, current: 2 mA < I < 15
mA
Off
Voltage: 0 V < V < 5 V, current: 15 mA max
Terminal wire area
0.2 .. 2.5 mm
2
Recommended tightening torque
0.5 .. 0.6 Nm
Communication
Terminal wire area
0.2 .. 2.5 mm
2
Recommended tightening torque
0.5 .. 0.6 Nm
Modbus-RTU
Up to 115.2 kbps
Environmental
Operating temperature
-5 - 55
Storage temperature
-40 - 85
Humidity
15 % up to 95 % without dew
Derating accepted operating altitude
4500 m
Without derating operating altitude
2000 m
Resistance to water and dust
HMI MP53/56: IP54
Main unit: IP20
Mechanical environment
Vibration 10 Hz-150 Hz, 1 g
Shock 11 ms, 15 g

Table of Contents