MOUNTING AND OPERATION MANUAL INDOOR AIR SWITCH-DISCONNECTOR, NAL/NALF/VR
13.0 Mounting of fuse-base
13.1 Mounting of fuse-base
When mounting a fuse-base with three post
insulators, one set of fuse contacts and possibly
fuse trip accessories are mounted directly on the
switch terminals, see Fig. 41 or 42.
3–6 mm
15 14 13
7 5 6
7
12
11
1
11
9
8
1 2 3 4
MEC.
10
max. e÷8 mm
e (DIN 43625)
41 Switch-disconnector type NALF mounted on the pivot side
43 Fuse tripping
44 Tripping rod
42 Switch-disconnector type NALF mounted on the oppening side
_
CAUTION!
1. The switch-disconnector must be
open and main springs not charged.
2. If contact plastic covers are added to
box with apparatus (component „A”
Fig.41), these covers must be
assembled at middle phase as shown
in the Fig.41.
_
WARNING!
These operations shall be carried out by
authorised personnel only!