NoteAction
Make sure that the safety related cables are
connected properly on both ends.
If the connection seems OK, proceed
with step 5.
If there is a problem with the connection,
proceed with step 11.
Check the safety related cable
connections: X15, X16, X17.
10
Make sure that the safety related cables are
connected properly on both ends.
If the connection seems OK, the fault has
been fixed. Proceed with step 1.
If there is a problem with the connection,
replace the safety related cables. See
12.
Restore the communication of the
safety related cables between the
modules by reconnecting the
cables X15, X16, X17.
11
If the connection seems OK, the fault has
been fixed. Proceed with step 1.
If the fault remains, see Troubleshooting
the power unit on page 382.
Replace the safety related cables:
X15, X16, X17.
12
Product manual - OmniCore V250XT 381
3HAC073447-001 Revision: B
© Copyright 2020-2022 ABB. All rights reserved.
7 Troubleshooting
7.3.3 Troubleshooting the drive unit
Continued