Note/IllustrationAction
Location of wrist strap button:
ELECTROSTATIC DISCHARGE
(ESD)
The unit is sensitive to ESD. Before
handling the unit read the safety inform-
ation in section The unit is sensitive to
ESD on page 45.
3
xx2300001842
Removing the drive unit
Note/IllustrationAction
Pull the cable ties out from the locking
holes.
Tip
Take photos of the cable ties and locking
holes before pulling out, to have as a
reference when refitting the cable ties.
1
Disconnect all connectors from the unit
to be replaced.
2
Lengthened screwdriverRemove the screws and pull the drive
unit out from the two guiding pins on the
mounting plate.
CAUTION
The cabling is sensitive to mechanical
damage. Handle it with care to avoid
damage to the cabling or the connector,
avoid any kind of tilt or skew.
3
xx2200001375
Continues on next page
266 Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
5 Repair
5.2.14 Replacing the additional drive unit