EasyManua.ls Logo

ABB OmniCore V400XT - Page 76

ABB OmniCore V400XT
466 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Examples
The following figure shows 2 examples on how protective earth and the signal
cable screens can be connected:
xx1200000960
Example 1:
Where a good earth connection is available on all units, the best shielding
is obtained by grounding all screens at both ends on all units.
Example 2:
If the cable is terminated where a good earth connection is not available a
noise suppression capacitor can be used. The screens of the 2 cables must
be connected as shown in the figure, but not connected to the chassis of the
unit.
Continues on next page
76 Product manual - OmniCore V400XT
3HAC081697-001 Revision: A
© Copyright 2022-2023 ABB. All rights reserved.
3 Installation and commissioning
3.5.2 Connecting cables to the controller
Continued

Table of Contents

Related product manuals