Technical data 125
Output side
Inverter type PRO-33.0-TL-OUTD-[-/S/SX]-400
AC grid connection type Three phase 3W + PE or 4W + PE
Rated AC power (P
AC, R
, @cos >0.99) 33,000 W
Maximum apparent power (S
max
) 33,000 VA
Rated AC grid voltage (V
AC, R
) 400 V
AC voltage range 320
…480 V
Range varies according to the country grid standard.
Rated AC output current (I
AC, R
) 47.8 A
Maximum AC output current (I
AC, max
) 50.3 A
Rated output frequency (f
R
)50Hz / 60Hz
Output frequency range (f
min
…f
max
)47…53 Hz / 57…63 Hz
Range varies according to the country grid standard.
Nominal power factor and adjustable
range
>0.995, with Pacr = 33.0 kW, adj. ±0.9 with Pacr =
29.7 kW, adj. ±0
…1 with S = 33.0 kVA
PQ diagram, with
- Over 95
…110% of the nominal grid voltage
- The DC voltage is over 580
…850 V
- The temperature is under 40 °C
Total current harmonic distortion < 3%
AC connector type Fixed plug, 4-pole + PE
AC connector ratings Conductor cross section 10
…25 mm
2
Cable diameter 22…32 mm (14...26 mm with reducer
seal)
Maximum current 125 A
Maximum voltage 630 V
AC
3633302724211815129630-3-6-9-12-15-18-21-24-27-30-33-36
36
33
30
27
24
21
18
15
12
9
6
3
0
PQ Diagram
Reactive Power (kVAr)
Active Power (kW)Active Power (kW)