86 Start-up
Relay output source values
Name/value Description
[0] Off The relay output activates when the inverter is off.
[1] Always on The relay output activates when the inverter is on.
[2] Fault The relay output activates when there is a fault.
[3] No Fault The relay output activates when there is no fault.
[4] Grid connected The relay output activates when there is grid connection.
[5] Grid not connected The relay output activates when there is no grid connection.
[6] Power level 20% The relay output activates when the output power is more than 20% of
the rated power.
[7] Power level 40% The relay output activates when the output power is more than 40% of
the rated power.
[8] Power level 70% The relay output activates when the output power is more than 70% of
the rated power.