EasyManua.ls Logo

ABB R-MAG 38kV 1250/2000A - Binary Outputs; Circuit Breaker Auxiliary Closed (KM1004 Pins 7 and 8); Circuit Breaker Auxiliary Open (KM1004 Pins 5 and 6); Circuit Breaker Closed (KM1004 Pins 3 and 4)

ABB R-MAG 38kV 1250/2000A
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
4. BINARY OUTPUTS
Binary outputs are simply pairs of mechanical wipe relay contacts. They can be employed to
switch in other circuitry or to an alarm indicator. See Apx Table 2 Output Contact Specifications
and Apx Figure 2 Electrical Load Curves for the power limitations of the contacts. Notice the flat
curve for AC voltage in Apx. Figure 2 Electrical Load Curves. On the inside of the low voltage
cabinet there is a membrane style button plate that contains a “Ready” LED. The Ready light
will either flash or turn off depending on the state of the capacitor voltage and coil continuity.
The “Unit Ready” output contact can be used to alarm for the more serious of the three types of
problems, but will not signal for all levels of the above problems. (see Apx Table 4 Circuit
Breaker Condition vs. Position)
4.1 Circuit Breaker Opened (KM1004 Pins 1 and 2)
The Circuit Breaker Opened contacts are normally open. They close only when the circuit
breaker is in the Open position.
4.2 Circuit Breaker Closed (KM1004 Pins 3 and 4)
The Circuit Breaker Closed contacts are normally open. They close only when the circuit
breaker is in the Closed position.
4.3 Circuit Breaker Auxiliary Open (KM1004 Pins 5 and 6)
The Circuit Breaker Auxiliary Open contacts close whenever the breaker is in the Open position.
4.4 Circuit Breaker Auxiliary Closed (KM1004 Pins 7 and 8)
An additional set of normally open contacts close whenever the breaker is in the Close position.
4.5 Unit Ready (KM1004 Pins 9 and 10)
These contacts are normally open. They close when the breaker is ready. They are used to
monitor capacitor charge (O-CO operation ready), valid circuit breaker position and coil
continuity.
4.6 Unit Not Ready (KM1004 Pins 11 and 12)
The Unit Not Ready contacts are normally closed. They open when the Unit is Ready. These
contacts are the inverse (negative) of the Unit Ready contacts.
When using the Not Ready contacts to provide an alarm to SCADA, an 8 second delay is
recommended since the unit will go to Not Ready when the capacitors are below 49 V. The 8
second delay allows the capacitors to charge prior to alarming.
4.7 Circuit Breaker Remote Open (KM1004 Pins 13 and 14)
The Circuit Breaker Remote Open contacts are referred to as the “Fleeting Output Contacts.”
This means that they only close for 100 milliseconds after a Remote Operation is performed.

Table of Contents

Related product manuals