EasyManua.ls Logo

ABB REB500 - Page 50

ABB REB500
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 6 1MRK 505 353-UEN
BP-Additions to base documentation
42 Application Manual
Bay protection functions REB500
Table 49 Directional overcurrent definite time protection 67 (PTOC)
Function/ Parameter Range/ Value
Current
0.02 to 20 I
N
in steps of 0.01 I
N
Angle -180° to +180° in steps of 15°
Delay
0.02 to 60 s in steps of 0.01 s
Wait time 0.02 to 20 s in steps of 0.01 s
Memory duration
0.2 to 60 s in steps of 0.01 s
Voltage input range
0.005 to 2 U
N
Voltage memory range
<0.005 U
N
Response time without delay
65 ms
· Directional overcurrent protection with detection of power flow direction
· Back-up protection
· 4 independent parameter sets
· Three-phase measurement
· Suppression of DC and HF components
· Definite time characteristic
· Voltage memory for near faults
· Selectable response when power direction no longer valid (trip or block)
Accuracies Classes/ Value
Accuracy of pick-up value ±5%
Accuracy of angle measurement (at 0.971.03 f
N
)
±5°
Reset ratio 95%