EasyManua.ls Logo

ABB REB650 - Page 104

ABB REB650
504 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PUREV
0.6 * IDirPU
PUFW
-RCA -85 deg
40% of
IDIR
IDIR
RCA
65 deg
Vpol = -V2
I = 3I
op 2
RCA +85 deg
RCA -85 deg
Characteristic
for PUREV
Operating area
Operating area
Characteristic
for PUFW
Characteristic for reverse
release of measuring steps
Characteristic for forward
release of measuring steps
-RCA +85 deg
ANSI11000269-2-en.ai
ANSI11000269 V2 EN
Figure 39: Operating characteristic for ground-fault directional element using the
negative sequence components
Two relevant setting parameters for directional supervision element are:
Directional element will be internally enabled to operate as soon as Iop is bigger
than 40% of IDirPU and directional condition is fulfilled in set direction.
Relay characteristic angle AngleRCA, which defines the position of forward and
reverse areas in the operating characteristic.
Directional comparison step, built-in within directional supervision element, will set
EF4PTOC (51N/67N) function output binary signals:
Section 7 1MRK 505 277-UUS C
Current protection
98
Technical Manual

Table of Contents

Other manuals for ABB REB650

Related product manuals