10.5.6 Operation principle
The PSTO input selects the operator place (LOCAL, REMOTE or ALL). One of the
eight outputs is activated based on the command sent from the operator place selected.
The settings Latchedx and tPulsex (where x is the respective output) will determine if
the signal will be pulsed (and how long the pulse is) or latched (steady). BLOCK will
block the operation of the function in case a command is sent, no output will be activated.
PSTO is the universal operator place selector for all control functions.
Although, PSTO can be configured to use LOCAL or ALL operator
places only, REMOTE operator place is used in SPC8GGIO function.
10.6 Automation bits AUTOBITS
10.6.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
AutomationBits, command function for
DNP3
AUTOBITS - -
10.6.2 Functionality
The Automation bits function (AUTOBITS) is used to configure the DNP3 protocol
command handling.