Name Values (Range) Unit Step Default Description
InfNo_2 1 - 255 - 1 2 Information number for output 2 (1-255)
InfNo_3 1 - 255 - 1 3 Information number for output 3 (1-255)
InfNo_4 1 - 255 - 1 4 Information number for output 4 (1-255)
InfNo_5 1 - 255 - 1 5 Information number for output 5 (1-255)
InfNo_6 1 - 255 - 1 6 Information number for output 6 (1-255)
InfNo_7 1 - 255 - 1 7 Information number for output 7 (1-255)
InfNo_8 1 - 255 - 1 8 Information number for output 8 (1-255)
10.10 Function commands generic for IEC 60870-5-103
I103GENCMD
10.10.1 Functionality
I103GENCMD is used for transmitting generic commands over IEC 60870-5-103. The
function has two outputs signals CMD_OFF and CMD_ON that can be used to
implement double-point command schemes.
10.10.2 Function block
IEC10000285-1-en.vsd
I103GENCMD
BLOCK ^CMD_OFF
^CMD_ON
IEC10000285 V1 EN
Figure 75: I103GENCMD function block
10.10.3 Signals
Table 126: I103GENCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of command
Table 127: I103GENCMD Output signals
Name
Type Description
CMD_OFF BOOLEAN Command output OFF
CMD_ON BOOLEAN Command output ON
1MRK 505 277-UUS C Section 10
Control
183