12.1.2.2 Function block
The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
CVMMXN
I3P*
V3P*
S
S_RANGE
P_INST
P
P_RANGE
Q_INST
Q
Q_RANGE
PF
PF_RANGE
ILAG
ILEAD
V
V_RANGE
I
I_RANGE
F
F_RANGE
ANSI10000051-1-en.vsd
ANSI10000051 V1 EN
Figure 97: CVMMXN function block
12.1.2.3 Signals
Table 178: CVMMXN Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- Three phase group signal for current inputs
V3P GROUP
SIGNAL
- Three phase group signal for voltage inputs
Table 179: CVMMXN Output signals
Name
Type Description
S REAL Apparent power magnitude of deadband value
S_RANGE INTEGER Apparent power range
P_INST REAL Active power
P REAL Active power magnitude of deadband value
P_RANGE INTEGER Active power range
Q_INST REAL Reactive power
Q REAL Reactive power magnitude of deadband value
Q_RANGE INTEGER Reactive power range
Table continues on next page
1MRK 505 277-UUS C Section 12
Monitoring
219
Technical Manual