Name Values (Range) Unit Step Default Description
PMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
PRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
QMin -2000.0 - 2000.0 %SB 0.1 -200.0 Minimum value in % of SBase
QMax -2000.0 - 2000.0 %SB 0.1 200.0 Maximum value in % of SBase
QRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VMin 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of UBase
VMax 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of UBase
VRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IMin 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table 181: CVMMXN Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
SDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
SZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
SHiHiLim 0.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SHiLim 0.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
SLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
Table continues on next page
1MRK 505 277-UUS C Section 12
Monitoring
221
Technical Manual

Table of Contents