Name Values (Range) Unit Step Default Description
PDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
PZeroDb 0 - 100000 m% 1 500 Zero point clamping
PHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
PLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
PLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
PLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
QDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
QZeroDb 0 - 100000 m% 1 500 Zero point clamping
QHiHiLim -2000.0 - 2000.0 %SB 0.1 150.0 High High limit in % of SBase
QHiLim -2000.0 - 2000.0 %SB 0.1 120.0 High limit in % of SBase
QLowLim -2000.0 - 2000.0 %SB 0.1 -120.0 Low limit in % of SBase
QLowLowLim -2000.0 - 2000.0 %SB 0.1 -150.0 Low Low limit in % of SBase
QLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
PFDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
PFZeroDb 0 - 100000 m% 1 500 Zero point clamping
PFHiHiLim -1.000 - 1.000 - 0.001 1.000 High High limit (physical value)
PFHiLim -1.000 - 1.000 - 0.001 0.800 High limit (physical value)
PFLowLim -1.000 - 1.000 - 0.001 -0.800 Low limit (physical value)
PFLowLowLim -1.000 - 1.000 - 0.001 -1.000 Low Low limit (physical value)
PFLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
VDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
VZeroDb 0 - 100000 m% 1 500 Zero point clamping
VHiHiLim 0.0 - 200.0 %VB 0.1 150.0 High High limit in % of UBase
VHiLim 0.0 - 200.0 %VB 0.1 120.0 High limit in % of UBase
VLowLim 0.0 - 200.0 %VB 0.1 80.0 Low limit in % of UBase
VLowLowLim 0.0 - 200.0 %VB 0.1 60.0 Low Low limit in % of UBase
VLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for
all limits)
IDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IZeroDb 0 - 100000 m% 1 500 Zero point clamping
IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
Table continues on next page