Table 184: CMMXU Output signals
Name Type Description
I_A REAL IA Amplitude
IA_RANGE INTEGER Phase A current magnitude range
IA_ANGL REAL IA Angle
I_B REAL IB Amplitude
IB_RANGE INTEGER Phase B current magnitude range
IB_ANGL REAL IB Angle
I_C REAL IC Amplitude
IC_RANGE INTEGER Phase C current magnitude range
IC_ANGL REAL IC Angle
12.1.3.4 Settings
Table 185: CMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
ILDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
ILMax 0 - 500000 A 1 1300 Maximum value
ILRepTyp Cyclic
Dead band
Int deadband
- - Dead band Reporting type
ILAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 186: CMMXU Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
ILZeroDb 0 - 100000 m% 1 500 Zero point clamping
ILHiHiLim 0 - 500000 A 1 1200 High High limit (physical value)
ILHiLim 0 - 500000 A 1 1100 High limit (physical value)
ILLowLim 0 - 500000 A 1 0 Low limit (physical value)
ILLowLowLim 0 - 500000 A 1 0 Low Low limit (physical value)
ILMin 0 - 500000 A 1 0 Minimum value
ILLimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
Table continues on next page
1MRK 505 277-UUS C Section 12
Monitoring
225
Technical Manual