12.8.6 Technical data
Table 232: DRPRDRE technical data
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
12.9 IEC 61850 generic communication I/O functions
SPGGIO
12.9.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
SPGGIO - -
12.9.2 Functionality
IEC61850 generic communication I/O functions (SPGGIO) is used to send one single
logical signal to other systems or equipment in the substation.
12.9.3 Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 117: SPGGIO function block
1MRK 505 277-UUS C Section 12
Monitoring
291
Technical Manual