12.18.3 Signals
Table 269: I103MEAS Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of service value reporting
I_A REAL 0.0 Service value for current phase A
I_B REAL 0.0 Service value for current phase B
I_C REAL 0.0 Service value for current phase C
IN REAL 0.0 Service value for residual current IN
V_A REAL 0.0 Service value for voltage phase A
V_B REAL 0.0 Service value for voltage phase B
V_C REAL 0.0 Service value for voltage phase C
V_AB REAL 0.0 Service value for voltage phase-phase A-B
V_N REAL 0.0 Service value for residual voltage VN
P REAL 0.0 Service value for active power
Q REAL 0.0 Service value for reactive power
F REAL 0.0 Service value for system frequency
12.18.4 Settings
Table 270: I103MEAS Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 1 Function type (1-255)
MaxIa 1 - 99999 A 1 3000 Maximum current phase A
MaxIb 1 - 99999 A 1 3000 Maximum current phase B
MaxIc 1 - 99999 A 1 3000 Maximum current phase C
MaxIN 1 - 99999 A 1 3000 Maximum residual current IN
MaxVa 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase A
MaxVb 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase B
MaxVc 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase C
MaxVa-Vb 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase A-B
MaxVn 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage VN
MaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active power
MaxQ 0.00 - 2000.00 MVA 0.05 1200.00 Maximum value for reactive power
MaxF 50.0 - 60.0 Hz 10.0 50.0 Maximum system frequency