13.1.4 Signals
Table 285: PCGGIO Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
READ_VAL BOOLEAN 0 Initiates an additional pulse counter reading
BI_PULSE BOOLEAN 0 Connect binary input channel for metering
RS_CNT BOOLEAN 0 Resets pulse counter value
Table 286: PCGGIO Output signals
Name Type Description
INVALID BOOLEAN The pulse counter value is invalid
RESTART BOOLEAN The reported value does not comprise a complete
integration cycle
BLOCKED BOOLEAN The pulse counter function is blocked
NEW_VAL BOOLEAN A new pulse counter value is generated
SCAL_VAL REAL Scaled value with time and status information
13.1.5 Settings
Table 287: PCGGIO Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
EventMask NoEvents
ReportEvents
- - NoEvents Report mask for analog events from pulse
counter
CountCriteria Off
RisingEdge
Falling edge
OnChange
- - RisingEdge Pulse counter criteria
Scale 1.000 - 90000.000 - 0.001 1.000 Scaling value for SCAL_VAL output to unit
per counted value
Quantity Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
- - Count Measured quantity for SCAL_VAL output
tReporting 1 - 3600 s 1 60 Cycle time for reporting of counter value
Section 13 1MRK 505 277-UUS C
Metering
346
Technical Manual