Time Synch Error
Internal Warning
GENTS SYNC ERROR
GENTS SYNC OK
S
R
GENTS RTC ERROR
S
R
OR
Internal Fail
LIODEV STOPPED
S
R
Real Time Clock Error
e.g.
BIO1- ERROR
Settings changed
SETTINGS CHANGED
RTE FATAL ERROR
WDOG STARVED
SW Watchdog Error
GENTS RTC OK
GENTS TIME RESET
OR
LIODEV STARTED
OR
LIODEV FAIL
OR
Runtime Exec Error
OR
RTE APP FAILED
S
R
RTE ALL APPS OK
OR
Setting groups changed
SETTINGS CHANGED
CHANGE LOCK ON
S
R
Change lock
CHANGE LOCK OFF
Runtime App Error
FTF FATAL ERROR
File System Error
S
R
IEC
61850
READY
DNP
3 STARTUP
ERROR
S
R
DNP
3
READY
IEC 61850 Error
IOM2- ERROR
DNP 3 Error
IEC 61850 NOT READY
ANSI09000381-1-en.vsd
ANSI09000381 V1 EN
Figure 159: Self supervision, function block internal signals
Some signals are available from the INTERRSIG function block. The signals from
INTERRSIG function block are sent as events to the station level of the control system.
The signals from the INTERRSIG function block can also be connected to binary
outputs for signalization via output relays or they can be used as conditions for other
functions if required/desired.
Individual error signals from I/O modules can be obtained from respective module in
the Signal Matrix tool. Error signals from time synchronization can be obtained from
the time synchronization block INTERRSIG.
Section 15 1MRK 505 277-UUS C
Basic IED functions
376