EQUATION1383 V4 EN-US (Equation 97)
21.1.7.2 Current transformers according to IEC 61869-2, class PX, PXR (and old
IEC 60044-6, class TPS and old British Standard, class X)
M11623-14 v5
CT
s according to these classes are specified approximately in the same way by a rated
knee point e.m.f. E
knee
(E
k
for class PX and PXR, E
kneeBS
for class X and the limiting
secondary voltage
V
al
for TPS). The value of the E
knee
is lower than the corresponding
E
al
according to IEC 61869-2. It is not possible to give a general relation between the
E
knee
and the E
al
but normally the E
knee
is approximately 80 % of the E
al
. Therefore,
the CTs according to class PX, PXR, X and TPS must have a rated knee point e.m.f.
E
knee
that fulfills the following:
(1 )= × + - ×
Old Calculated
S TD S TD S
EQUATION1893.ANSI V1 EN-US (Equation 98)
21.1.7.3 Current transformers according to ANSI/IEEE
M11623-22 v6
Current transformers according to ANSI/IEEE are partly specified in different ways. A
rated secondary terminal voltage
V
ANSI
is specified for a CT of class C. V
ANSI
is the
secondary terminal voltage the CT will deliver to a standard burden at 20 times rated
secondary current without exceeding 10 % ratio correction. There are a number of
standardized V
ANSI
values for example, V
ANSI
is 400 V for a C400 CT. A
corresponding rated equivalent limiting secondary e.m.f. E
alANSI
can be estimated as
follows:
a lANSI SN CT ANS I S N CT SN bANS I
E 20 I R V 20 I R 20 I Z= × × + = × × + × ×
EQUATION1682 V1 EN-US (Equation 99)
where:
Z
bANSI
The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific C
class (W)
V
ANSI
The secondary terminal voltage for the specific C class (V)
The CTs according to class C must have a calculated rated equivalent limiting
secondary e.m.f. E
alANSI
that fulfils the following: