16. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REB670*1.2-A20X01-C06-X0-A-A-B-A-A2-X0-CAX-XXX-XD. Using the code of each position #1-12 specified as REB670*1-2 2-3 3 3-4-5-6-7 7-8-9 9
9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12
# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 -
REB670* - - - - - . - -
10 - 11 - 12
. -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no
1.2
Selection for position #1.
Configuration alternatives #2 Notes and Rules
3 phase, 4 bays A20
3 phase, 8 bays A31
1 phase, 12 bays, 1/2 19" case B20
1 phase, 12 bays, 1/1 19" case B21
1 phase, 24 bays B31
ACT configuration
Simple station layout, 1 1/2 CB, 2 CB, 1 CB, b-contacts, BBP only X01
Double busbar - 1 CB, a and b contacts, BBP only X02 Note: Only for A31, B21 and B31
Double busbar - 1 CB, a and b contacts, BBP, EnFP X03 Note: Only for A31, B21 and B31
Note: One each of Breaker failure
protection and Overcurrent
protection must be ordered
Selection for position #2.
Software options #3 Notes and Rules
No option X00 All fields in the ordering form do
not need to be filled in
Four step phase overcurrent protection, 4 bays C06 Note: Only for A20
Four step phase overcurrent protection, 8 bays C07 Note: Only for A31
Four step single phase overcurrent protection, 12 bays C08 Note: Only for B20 and B21
Four step single phase overcurrent protection, 24 bays C09 Note: Only for B31
Breaker failure protection, 4 bays C10 Note: Only for A20
Breaker failure protection, 8 bays C11 Note: Only for A31
Breaker failure protection, 12 bays, single phase C12 Note: Only for B20 and B21
Breaker failure protection, 24 bays, single phase C13 Note: Only for B31
Autorecloser, 2 circuit breakers H05
IEC 62439-3 Edition 1, parallel redundancy protocol P01 Note:Require 2-channel OEM
IEC 62439-3 Edition 2, parallel redundancy protocol P02
Selection for position #3
1MRK505212-BEN E
Pre-configured
Product version: 1.2
54 ABB