7.4.7 Technical data
Table 134: LOVPTUV (27) technical data
Function
Range or value Accuracy
Operate voltage (0–100)% of VBase ± 0.5% of V
n
Reset ratio <105% -
Pulse timer (0.050–60.000) s ± 0.5% ± 25 ms
Timers (0.000–60.000) s ± 0.5% ± 25 ms
Section 7 1MRK 511 287-UUS A
Voltage protection
190
Technical manual

Table of Contents