Name Values (Range) Unit Step Default Description
3I2PU 1 - 100 %IB 1 10 Pickup of negative sequence undercurrent
element in % of IBase
OpDVDI Disabled
Enabled
- - Disabled Operation of change based function Disable/
Enable
DVPU 1 - 100 %VB 1 60 Pickup of change in phase voltage in % of
VBase
DIPU 1 - 100 %IB 1 15 Pickup of change in phase current in % of
IBase
VPPU 1 - 100 %VB 1 70 Pickup of phase voltage in % of VBase
50P 1 - 100 %IB 1 10 Pickup of phase current in % of IBase
SealIn Disabled
Enabled
- - Enabled Seal in functionality Disable/Enable
VSealInPU 1 - 100 %VB 1 70 Pickup of seal-in phase voltage in % of VBase
IDLDPU 1 - 100 %IB 1 5 Pickup for phase current detection in % of
IBase for dead line detection
VDLDPU 1 - 100 %VB 1 60 Pickup for phase voltage detection in % of
VBase for dead line detection
Table 158: SDDRFUF Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
9.2.6 Monitored data
Table 159: SDDRFUF Monitored data
Name
Type Values (Range) Unit Description
3I0 REAL - A Magnitude of zero sequence
current
3I2 REAL - A Magnitude of negative
sequence current
3V0 REAL - kV Magnitude of zero sequence
voltage
3V2 REAL - kV Magnitude of negative
sequence voltage
1MRK 511 287-UUS A Section 9
Secondary system supervision
209