EasyManua.ls Logo

ABB REC650 ANSI - Technical Data

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 93: Simplified logic diagram for fuse failure supervision function, Main logic
9.2.8 Technical data
Table 160: SDDRFUF technical data
Function Range or value Accuracy
Operate voltage, zero sequence (1-100)% of VBase ± 1.0% of V
n
Operate current, zero sequence (1–100)% of IBase ± 1.0% of I
n
Operate voltage, negative sequence (1–100)% of VBase ± 0.5% of V
n
Operate current, negative sequence (1–100)% of IBase ± 1.0% of I
n
Operate voltage change pickup (1–100)% of VBase ± 5.0% of V
n
Operate current change pickup (1–100)% of IBase ± 5.0% of I
n
Operate phase voltage (1-100)% of VBase ± 0.5% of V
n
Operate phase current (1-100)% of IBase ± 1.0% of I
n
Operate phase dead line voltage (1-100)% of VBase ± 0.5% of V
n
Operate phase dead line current (1-100)% of IBase ± 1.0% of I
n
9.3 Breaker close/trip circuit monitoring TCSSCBR
9.3.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker close/trip circuit monitoring TCSSCBR - -
9.3.2 Functionality
The trip circuit supervision function TCSSCBR is designed to supervise the control circuit
of the circuit breaker. The trip circuit supervision generates a current of approximately 1
mA through the supervised control circuit. The validity supervision of a control circuit is
provided for power output contacts T1, T2 and T3.
The function picks up and trips when TCSSCBR detects a trip circuit failure. The trip time
characteristic for the function is of definite time (DT) type. The function trips after a
predefined operating time and resets when the fault disappears.
Section 9 1MRK 511 287-UUS A
Secondary system supervision
218
Technical manual

Table of Contents

Related product manuals