ABB REC650 ANSI - Synchronizing

ABB REC650 ANSI
700 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TSTSC
BLKSC
BLOCK
T
S
T
A
U
T
S
Y
AUTOSYOK
P
H
D
I
F
F
M
E
FRDIFFME
VDIFFME
PHDIFFA
VOKSC
VDIFFSC
OR
AND
AND
AND
AND
AND
AND
phaseAngleDifferenceValue
frequencyDifferenceValue
voltageDifferenceValue
1
1
AND
Note! Similar logic for Manual Synchrocheck.
1
FRDIFFA
ANSI08000018-2-en.vsd
OperationSC = Enabled
VDiffSC
FreqDiffA
PhaseDiffA
Bus voltage >80%
of GblBaseSelBus
Line voltage >80%
of GblBaseSelLine
PhaseDiff > 60°
100 ms
INADVCLS
AND
AND
PhaseDiff < 5°
0
0-tSCA
0
50 ms
80 ms
0
ANSI08000018 V2 EN
Figure 97: Simplified logic diagram for the Auto Synchronism function
10.1.7.3 Synchronizing
When the function is set to OperationSynch = Enabled the measuring will be performed.
The function will compare the values for the bus and line voltage with internally preset
values that are set to be 80% of the set UBase selected for GlbBaseSelBus and
GlbBaseSelLine, which is a supervision that the voltages are both live. Also the voltage
difference is checked to be smaller than the internally preset value 0.10, which is a p.u
value of set voltage base values. If both sides are higher than the preset values and the
1MRK 511 287-UUS A Section 10
Control
229
Technical manual