phaseAngleDifferenceValue
frequencyDifferenceValue
voltageDifferenceValue
1
1
AND
Note! Similar logic for Manual Synchrocheck.
1
FRDIFFA
ANSI08000018-2-en.vsd
OperationSC = Enabled
VDiffSC
FreqDiffA
PhaseDiffA
Bus voltage >80%
of GblBaseSelBus
Line voltage >80%
of GblBaseSelLine
PhaseDiff > 60°
100 ms
INADVCLS
AND
AND
PhaseDiff < 5°
0
0-tSCA
0
50 ms
80 ms
0
ANSI08000018 V2 EN
Figure 97: Simplified logic diagram for the Auto Synchronism function
10.1.7.3 Synchronizing
When the function is set to OperationSynch = Enabled the measuring will be performed.
The function will compare the values for the bus and line voltage with internally preset
values that are set to be 80% of the set UBase selected for GlbBaseSelBus and
GlbBaseSelLine, which is a supervision that the voltages are both live. Also the voltage
difference is checked to be smaller than the internally preset value 0.10, which is a p.u
value of set voltage base values. If both sides are higher than the preset values and the
1MRK 511 287-UUS A Section 10