Name Type Description
WFMASTER BOOLEAN Signal to Slave issued by Master for sequential
reclosing
COUNT3P1 INTEGER Counting the number of three-phase reclosing shot 1
COUNT3P2 INTEGER Counting the number of three-phase reclosing shot 2
COUNT3P3 INTEGER Counting the number of three-phase reclosing shot 3
COUNT3P4 INTEGER Counting the number of three-phase reclosing shot 4
COUNT3P5 INTEGER Counting the number of three-phase reclosing shot 5
COUNTAR INTEGER Counting total number of reclosing shots
10.2.5 Settings
Table 173: SMBRREC (79) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
External ctrl
Enabled
-
- External ctrl Disable/ExternalCtrl/Enable
t1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing 3ph
tReset 0.00 - 6000.00 s 0.01 60.00 Duration of the reset time
tSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchronism-check OK
tTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse duration
tCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that CB must be closed before
new sequence allows
tUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicating
Unsuccessful/Successful
Priority None
Low
High
-
- None Priority selection between adjacent terminals
None/Low/High
tWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from Master
Table 174: SMBRREC (79) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
NoOfShots 1
2
3
4
5
-
- 1 Maximum number of reclosing shots 1-5
StartByCBOpen Disabled
Enabled
- - Disabled To be set ON if AR is to be started by CB open
position
CBAuxContType NormClosed
NormOpen
- - NormOpen Select CB auxilary contact type NC/NO for
CBPOS input
Table continues on next page