10.4.7.5 Signals
Table 209: BH_CONN (3) Input signals
Name
Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
6189_OP BOOLEAN 0 6189 is in open position
6189_CL BOOLEAN 0 6189 is in closed position
6289_OP BOOLEAN 0 6289 is in open position
6289_CL BOOLEAN 0 6289 is in closed position
189G_OP BOOLEAN 0 189G is in open position
189G_CL BOOLEAN 0 189G is in closed position
289G_OP BOOLEAN 0 289G is in open position
289G_CL BOOLEAN 0 289G is in closed position
1389G_OP BOOLEAN 0 1389G on line 1 is in open position
1389G_CL BOOLEAN 0 1389G on line 1 is in closed position
2389G_OP BOOLEAN 0 2389G on line 2 is in open position
2389G_CL BOOLEAN 0 2389G on line 2 is in closed position
6189_EX1 BOOLEAN 0 External condition for apparatus 6189
6189_EX2 BOOLEAN 0 External condition for apparatus 6189
6289_EX1 BOOLEAN 0 External condition for apparatus 6289
6289_EX2 BOOLEAN 0 External condition for apparatus 6289
Table 210: BH_LINE_A (3) Input signals
Name
Type Default Description
152_OP BOOLEAN 0 152 is in open position
152_CL BOOLEAN 0 152 is in closed position
689_OP BOOLEAN 0 689 is in open position
689_CL BOOLEAN 0 689 is in closed position
189_OP BOOLEAN 0 189 is in open position
189_CL BOOLEAN 0 189 is in closed position
189G_OP BOOLEAN 0 189G is in open position
189G_CL BOOLEAN 0 189G is in closed position
289G_OP BOOLEAN 0 289G is in open position
289G_CL BOOLEAN 0 289G is in closed position
389G_OP BOOLEAN 0 389G is in open position
389G_CL BOOLEAN 0 389G is in closed position
Table continues on next page
Section 10 1MRK 511 287-UUS A
Control
308