Table 220: DB_LINE (3) Output signals
Name Type Description
989REL BOOLEAN Switching of 989 is allowed
989ITL BOOLEAN Switching of 989 is not allowed
389GREL BOOLEAN Switching of 389G is allowed
389GITL BOOLEAN Switching of 389G is not allowed
989GREL BOOLEAN Switching of 989G is allowed
989GITL BOOLEAN Switching of 989G is not allowed
10.4.8.6 Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
10.4.9 Interlocking for line bay ABC_LINE (3)
10.4.9.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for line bay ABC_LINE - 3
10.4.9.2 Functionality
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure 147. The function
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
1MRK 511 287-UUS A Section 10
Control
323
Technical manual