10.7.3 Function block
DPGGIO
OPEN
CLOSE
VALID
POSITION
IEC09000075_1_en.vsd
IEC09000075 V1 EN
Figure 155: DPGGIO function block
10.7.4 Signals
Table 234: DPGGIO Input signals
Name Type Default Description
OPEN BOOLEAN 0 Open indication
CLOSE BOOLEAN 0 Close indication
VALID BOOLEAN 0 Valid indication
Table 235: DPGGIO Output signals
Name Type Description
POSITION INTEGER Double point indication
10.7.5 Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
10.7.6 Operation principle
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment or
system that requests these signals. To be able to get the signals, PCM600 must be used to
define which function block in which equipment or system should receive this
information.