Section 11 Logic
11.1 Tripping logic common 3-phase output SMPPTRC (94)
11.1.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Tripping logic common 3-phase output SMPPTRC
SYMBOL-K V1 EN
94
11.1.2 Functionality
A function block for protection tripping is provided for each circuit breaker involved in
the tripping of the fault. It provides a settable pulse prolongation to ensure a three-phase
trip pulse of sufficient length, as well as all functionality necessary for correct co-
operation with autoreclosing functions.
The trip function block also includes a settable latch functionality for breaker lock-out.
11.1.3 Function block
ANSI09000284-1-en.vsd
SMPPTRC (94)
BLOCK
TRINP_3P
SETLKOUT
RSTLKOUT
TRIP
CLLKOUT
ANSI09000284 V1 EN
Figure 163: SMPPTRC (94) function block
1MRK 511 287-UUS A Section 11
Logic
365
Technical manual