Name of input Type Default Description Value when
activated
Value when
deactivated
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16)
are active that is=1; is 65535. 65535 is the highest boolean value that can be converted to
an integer by the B16I function block.
11.6 Boolean 16 to integer conversion with logic node
representation B16IFCVI
11.6.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion with
logic node representation
B16IFCVI - -
11.6.2 Functionality
Boolean 16 to integer conversion with logic node representation function B16IFCVI is
used to transform a set of 16 binary (logical) signals into an integer. The block input will
freeze the output at the last value.
Section 11 1MRK 511 287-UUS A
Logic
404
Technical manual