tAlarm and tWarning are user settable limits. They are also independent, that is, there is
no check if tAlarm > tWarning.
tAlarm and tWarning are possible to be defined with a resolution of 10 ms, depending on
the level of the defined values for the parameters.
tOverflow is for the overflow supervision with a default value tOverflow = 999 999.9
seconds. The outputs freeze if an overflow occurs.
11.9.6.1 Operation Accuracy
The accuracy of TEIGGIO depends on essentially three factors
• task cycle time
• the pulse length
• the number of pulses, that is the number of rising and falling flank pairs
In principle, a shorter task cycle time, longer integrated time length or more pulses may
lead to reduced accuracy.
11.9.6.2 Memory storage
The value of the integrated elapsed time is retained in a non-volatile memory, only if any
warning, alarm or/and overflow occurs. Consequently there is a risk of data loss in the
integrated time at a power failure.
11.9.7 Technical data
Table 336: TEIGGIO Technical data
Function
Cycle time (ms) Range or value Accuracy
Elapsed time integration 5 0 ~ 999999.9 s ±0.05% or ±0.01 s
20 0 ~ 999999.9 s ±0.05% or ±0.04 s
100 0 ~ 999999.9 s ±0.05% or ±0.2 s
1MRK 511 287-UUS A Section 11
Logic
417
Technical manual