Name Values (Range) Unit Step Default Description
IHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBase
IHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBase
ILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBase
ILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBase
ILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for all
limits)
FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
FrZeroDb 0 - 100000 m% 1 500 Zero point clamping
FrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)
FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)
FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)
FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)
FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for all
limits)
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 5% of
Vn
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 30% of
Vn
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of In
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30% of
In
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%
of In
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
12.1.2.5 Monitored data
Table 341: CVMMXN Monitored data
Name
Type Values (Range) Unit Description
S REAL - MVA Apparent power magnitude of
deadband value
P REAL - MW Active power magnitude of
deadband value
Q REAL - MVAr Reactive power magnitude of
deadband value
Table continues on next page
1MRK 511 287-UUS A Section 12
Monitoring
425
Technical manual