Name Type Description
VB_RANGE INTEGER V_B Amplitude range
VB_ANGL REAL V_B Angle, magnitude of reported value
V_C REAL V_C Amplitude, magnitude of reported value
VC_RANGE INTEGER V_C Amplitude range
VC_ANGL REAL VC Angle, magnitude of reported value
12.1.7.4 Settings
Table 364: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
GlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Value
groups
VDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
VMax 0 - 2000000 V 1 106000 Maximum value
VRepTyp Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
VLimHys 0.000 - 100.000 V 0.001 5.000 Hysteresis value in % of range and is common
for all limits
VAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, Int
Db: In %s
Table 365: VNMMXU Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
VZeroDb 0 - 100000 m% 1 500 Zero point clamping in 0.001% of range
VHiHiLim 0 - 2000000 V 1 96000 High High limit (physical value)
VHiLim 0 - 2000000 V 1 86000 High limit (physical value)
VLowLim 0 - 2000000 V 1 71000 Low limit (physical value)
VLowLowLim 0 - 2000000 V 1 66000 Low Low limit (physical value)
VMin 0 - 2000000 V 1 0 Minimum value