14.4.5 Operation principle
The OUTxVAL output, where 1≤x≤16, will be HIGH if the incoming message is with
valid data.
The OUTxVAL output contains both quality validity and communication validity since
GOOSEBINRCV function has no COMMVALID output.
The input of this GOOSE block must be linked in SMT by means of a cross
to receive the binary values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the OUTxVAL output
will be HIGH. If quality data validity is INVALID, QUESTIONABLE,
OVERFLOW, FAILURE or OLD DATA then the OUTxVAL output will
be LOW.
14.5 GOOSE function block to receive a double point value
GOOSEDPRCV
14.5.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
double point value
GOOSEDPRCV - -
14.5.2 Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
1MRK 511 287-UUS A Section 14
Station communication
569
Technical manual