14.5.3 Function block
IEC10000249-1-en.vsd
GOOSEDPRCV
BLOCK ^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249 V1 EN
Figure 256: GOOSEDPRCV function block
14.5.4 Signals
Table 468: GOOSEDPRCV Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
Table 469: GOOSEDPRCV Output signals
Name Type Description
DPOUT INTEGER Double point output
DATAVALID BOOLEAN Data valid for double point output
COMMVALID BOOLEAN Communication valid for double point output
TEST BOOLEAN Test output
14.5.5 Settings
Table 470: GOOSEDPRCV Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
14.5.6 Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Section 14 1MRK 511 287-UUS A
Station communication
570
Technical manual