16.2 Inputs
16.2.1 Measuring inputs
Table 529: Analog input modules TRM
Terminal TRM
6I + 4U
TRM
8I + 2U
TRM
4I + 1I + 5U
TRM
4I + 6U
X101-1, 2 1/5A 1/5A 1/5A 1/5A
X101-3, 4 1/5A 1/5A 1/5A 1/5A
X101-5, 6 1/5A 1/5A 1/5A 1/5A
X101-7, 8 1/5A 1/5A 1/5A 1/5A
X101-9, 10 1/5A 1/5A 0.1/0.5A 100/220V
X102-1, 2 1/5A 1/5A 100/220V 100/220V
X102-3, 4 100/220V 1/5A 100/220V 100/220V
X102-5, 6 100/220V 1/5A 100/220V 100/220V
X102-7, 8 100/220V 100/220V 100/220V 100/220V
X102-9, 10 100/220V 100/220V 100/220V 100/220V
Table 530: Analog input modules AIM
Terminal
AIM
6I + 4U
AIM
4I + 1I + 5U
X103-1, 2 1/5A 1/5A
X103-3, 4 1/5A 1/5A
X103-5, 6 1/5A 1/5A
X103-7, 8 1/5A 1/5A
X103-9, 10 1/5A 0.1/0.5A
X104-1, 2 1/5A 100/220V
X104-3, 4 100/220V 100/220V
X104-5, 6 100/220V 100/220V
X104-7, 8 100/220V 100/220V
X104-9, 10 100/220V 100/220V
See the connection diagrams for information on the analog input module
variant included in a particular configured IED. The primary and
secondary rated values of the primary VT's and CT's are set for the analog
inputs of the IED.
Section 16 1MRK 511 287-UUS A
IED physical connections
632
Technical manual