Z
A
Z
B
Z
L1
A B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
ANSI09000025_2_en.vsd
ANSI09000025 V2 EN
Figure 42: Two parallel lines. Influence from parallel line to the through fault current:
I
M
The minimum theoretical current setting (Imin) will in this case be:
I m in M A X I
fA
I
fB
I
M
, ,( )³
EQUATION287 V1 EN (Equation 36)
Where:
I
fA
and I
fB
have been described for the single line case.
Considering the safety margins mentioned previously, the minimum setting (Is) is:
m
1.3.Is inI ³
EQUATION288 V2 EN (Equation 37)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (IBase).
Operation: set the protection to Enabled or Disabled.
Pickup: Set operate current in % of IBase. IBase is a global parameter valid for all
functions in the IED.
1MRK 511 286-UUS A Section 6
Current protection
105
Application manual