ANSI05000150_2_en.vsd
67
N
One- or two-phase ground-fault
67N
0
3I
ANSI05000150 V2 EN
Figure 46: Step 1, first calculation
The residual current out on the line is calculated at a fault on the remote busbar (one- or
two-phase-to-ground fault). To assure selectivity it is required that step 1 shall not give a
trip at this fault. The requirement can be formulated according to equation 38.
step1 0I 1.2 3I (remote busbar)³ ×
EQUATION1199 V3 EN (Equation 38)
As a consequence of the distribution of zero sequence current in the power system, the
current to the protection might be larger if one line out from the remote busbar is taken out
of service, see figure
47.
en05000151_ansi.vsd
67N
One- or two-phase-ground-fault
0
3I
ANSI05000151 V2 EN
Figure 47: Step 1, second calculation. Remote busbar with, one line taken out of
service
Section 6 1MRK 511 286-UUS A
Current protection
114
Application manual