6.11.2.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional overpower protection GOPPDOP
P >
2
DOCUMENT172362-IMG158942
V2 EN
32
6.11.2.2 Setting guidelines
GlobalBaseSel: Selects the global base value group used by the function to define (IBase),
(VBase) and (SBase).
Operation: With the parameter Operation the function can be set Enabled/Disabled.
Mode: The voltage and current used for the power measurement. The setting possibilities
are shown in table
11.
For reverse power applications PosSeq or Arone modes are strongly recommended.
Table 11: Complex power calculation
Set value
Mode
Formula used for complex power calculation
A,B,C
* * *
A B C
A B C
S V I V I V I= × + × + ×
EQUATION2038 V1 EN (Equation 59)
Arone
* *
A C
AB BC
S V I V I= × ×-
EQUATION2039 V1 EN (Equation 60)
PosSeq
*
PosSeq
PosSeq
S 3 V I= × ×
EQUATION2040 V1 EN (Equation 61)
A,B
*
A B
AB
*
S V (I I )= × -
EQUATION2041 V1 EN (Equation 62)
B,C
*
B C
BC
*
S V (I I )= × -
EQUATION2042 V1 EN (Equation 63)
C,A
*
C A
CA
*
S V (I I )= × -
EQUATION2043 V1 EN (Equation 64)
Table continues on next page
1MRK 511 286-UUS A Section 6