Set value
Mode
Formula used for complex power calculation
A
EQUATION2044 V1 EN (Equation 65)
B
EQUATION2045 V1 EN (Equation 66)
C
EQUATION2046 V1 EN (Equation 67)
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
Section 6 1MRK 511 286-UUS A
Current protection
142
Application manual