Table 84: T_F32_INT8 Output signal
Name Type Description
INT8 INT8 Output signal
3.13.5.4 Settings
The function does not have any parameters available in LHMI or Protection and
Control IED Manager (PCM600).
3.13.6 T_DIR function block
3.13.6.1 Functionality
The T_DIR function evaluates enumerated data of the FAULT_DIR data attribute
of the directional functions. T_DIR can only be used with GOOSE. The DIR input
can be connected to the GOOSERCV_ENUM function block, which is receiving
the LD0.<function>.Str.dirGeneral or LD0.<function>.Dir.dirGeneral data attribute
sent by another IED.
The outputs FWD and REV are extracted from the enumerated input value.
3.13.6.2 Signals
Table 85: T_DIR Input signals
Name
Type Default Description
DIR Enum 0 Input signal
Table 86: T_DIR Output signals
Name
Type Default Description
FWD BOOLEAN 0 Direction forward
REV BOOLEAN 0 Direction backward
1YHT530004D05 D Section 3
Basic functions
615 series 107
Technical Manual