Table 126: PTGAPC Output signals
Name Type Description
Q1 BOOLEAN Output 1 status
Q2 BOOLEAN Output 2 status
Q3 BOOLEAN Output 3 status
Q4 BOOLEAN Output 4 status
Q5 BOOLEAN Output 5 status
Q6 BOOLEAN Output 6 status
Q7 BOOLEAN Output 7 status
Q8 BOOLEAN Output 8 status
3.14.3.4 Settings
Table 127: PTGAPC Non group settings
Parameter Values (Range) Unit Step Default Description
Pulse delay time 1 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 2 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 3 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 4 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 5 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 6 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 7 0...3600000 ms 10 0 Pulse delay time
Pulse delay time 8 0...3600000 ms 10 0 Pulse delay time
3.14.3.5 Technical data
Table 128: PTGAPC Technical data
Characteristic
Value
Operate time accuracy ±1.0% of the set value or ±20 ms
Section 3 1YHT530004D05 D
Basic functions