Table 226: DPH3HPDOC Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Reset delay time 0...60000 ms 10 20 Reset delay time
Minimum operate time 20...60000 ms 10 20 Minimum operate time for IDMT curves
Allow Non Dir 0=False
1=True
0=False Allows prot activation as non-dir when dir
info is invalid
Measurement mode 1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used measurement mode
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating current
Min operate voltage 0.01...1.00 xUn 0.01 0.01 Minimum operating voltage
Curve parameter A 0.0086...120.0000 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 0.1217 Parameter B for customer programmable
curve
Curve parameter C 0.02...2.00 2.00 Parameter C for customer
programmable curve
Curve parameter D 0.46...30.00 29.10 Parameter D for customer
programmable curve
Curve parameter E 0.0...1.0 1.0 Parameter E for customer programmable
curve
Num of start phases 1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3 Number of phases required for operate
activation
4.1.4.10 Monitored data
Table 227: DPH3LPDOC Monitored data
Name
Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
DIRECTION Enum 0=unknown
1=forward
2=backward
3=both
Direction information
DIR_A Enum 0=unknown
1=forward
2=backward
3=both
Direction phase A
DIR_B Enum 0=unknown
1=forward
2=backward
3=both
Direction phase B
Table continues on next page
1YHT530004D05 D Section 4
Protection functions
615 series 223
Technical Manual