EasyManua.ls Logo

ABB RED615 - Monitored Data

ABB RED615
896 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 312: INTRPTEF Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Operation mode 1=Intermittent EF
2=Transient EF
1=Intermittent EF Operation criteria
Reset delay time 40...60000 ms 1 500 Reset delay time
Peak counter limit 2...20 2 Min requirement for peak counter before
start in IEF mode
Min operate current 0.01...1.00 xIn 0.01 0.01 Minimum operating current for transient
detector
4.2.3.8 Monitored data
Table 313: INTRPTEF Monitored data
Name Type Values (Range) Unit Description
FAULT_DIR Enum 0=unknown
1=forward
2=backward
3=both
Detected fault direction
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
INTRPTEF Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.2.3.9 Technical data
Table 314: INTRPTEF Technical data
Characteristic
Value
Operation accuracy (Uo criteria with transient
protection)
Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x Uo
Operate time accuracy ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5
Section 4 1YHT530004D05 D
Protection functions
310 615 series
Technical Manual

Table of Contents

Other manuals for ABB RED615

Related product manuals