Table 343: TR2PTDF Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off/On
CT connection type 1=Type 1
2=Type 2
1=Type 1 CT connection type. Determined by the
directions of the connected current
transformers
Winding 1 type 1=Y
2=YN
3=D
4=Z
5=ZN
1=Y Connection of the HV side windings
Winding 2 type 1=y
2=yn
3=d
4=z
5=zn
1=y Connection of the LV side windings
Clock number 0=Clk Num 0
1=Clk Num 1
2=Clk Num 2
4=Clk Num 4
5=Clk Num 5
6=Clk Num 6
7=Clk Num 7
8=Clk Num 8
10=Clk Num 10
11=Clk Num 11
0=Clk Num 0 Setting the phase shift between HV and
LV with clock number for connection
group compensation (e.g. Dyn11 -> 11)
Zro A elimination 1=Not eliminated
2=Winding 1
3=Winding 2
4=Winding 1 and 2
1=Not eliminated Elimination of the zero-sequence current
Min winding tap -36...36 1 36 The tap position number resulting the
minimum number of effective winding
turns on the side of the transformer
where the tap changer is.
Max winding tap -36...36 1 0 The tap position number resulting the
maximum number of effective winding
turns on the side of the transformer
where the tap changer is.
Tap nominal -36...36 1 18 The nominal position of the tap changer
resulting the default transformation ratio
of the transformer (as if there was no tap
changer)
Tapped winding 1=Not in use
2=Winding 1
3=Winding 2
1=Not in use The winding where the tap changer is
connected to
Step of tap 0.60...9.00 % 0.01 1.50 The percentage change in voltage
corresponding one step of the tap changer
CT ratio Cor Wnd 1 0.40...4.00 0.01 1.00 CT ratio correction, winding 1
CT ratio Cor Wnd 2 0.40...4.00 0.01 1.00 CT ratio correction, winding 2
1YHT530004D05 D Section 4
Protection functions
615 series 419
Technical Manual