Table 24: Serial communication settings
Parameter Values (Range) Unit Step Default Description
Fiber mode 0=No fiber
2=Fiber optic
0=No fiber Fiber mode for COM2
Serial mode 1=RS485 2Wire
2=RS485 4Wire
3=RS232 no
handshake
4=RS232 with
handshake
1=RS485 2Wire Serial mode for COM2
CTS delay 0...60000 0 CTS delay for COM2
RTS delay 0...60000 0 RTS delay for COM2
Baudrate 1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
6=9600 Baudrate for COM2
Table 25: Time settings
Parameter
Values (Range) Unit Step Default Description
Date 0 Date
Time 0 Time
Time format 1=24H:MM:SS:MS
2=12H:MM:SS:MS
1=24H:MM:SS:M
S
Time format
Date format 1=DD.MM.YYYY
2=DD/MM/YYYY
3=DD-MM-YYYY
4=MM.DD.YYYY
5=MM/DD/YYYY
6=YYYY-MM-DD
7=YYYY-DD-MM
8=YYYY/DD/MM
6=YYYY-MM-DD Date format
Local time offset -720...720 min 480 Local time offset in minutes
Synch source 0=None
1=SNTP
2=Modbus
5=IRIG-B
8=Line differential
9=DNP
17=IEC60870-5-10
3
1=SNTP Time synchronization source
IP SNTP primary 10.58.125.165 IP address for SNTP primary server
IP SNTP secondary 192.168.2.165 IP address for SNTP secondary server
DST on time 02:00 Daylight savings time on, time (hh:mm)
DST on date 01.05 Daylight savings time on, date (dd.mm)
Table continues on next page